Flame Scanner Type 45RM4 + DP 7000 digital profiling amplifier


PROJECT: Hydrogen Sulfide Incinerator Replacement for Geothermal Generation


A large number of generating units were installed in the Geysers area around Clear Lake, CA, while PG&E owned these facilities. A by-product of using the steam out of the ground is the off gassing of hydrogen sulfide (H2S) gas which has a strong odor of rotten eggs. While PG&E owned these units, the local air pollution control district implement regulations to control release of H2S gas. PG&E had their Department of Engineering Research build a pilot incinerator at one of the generating site's location. In the year 2000, this pilot incinerator was at least 5 years old and was failing. An independent power producer (IPP) purchased the majority of PG&E's geysers units and also bought a used incinerator of much larger capacity to replace the pilot incinerator. The used incinerator system consisted of a simple antiquated hardwired analog control system using basic control theory to maintain combustion and quenching water flow rates.

The IPP requested that the control system be upgraded to an Allen-Bradley ControlLogix PLC including building the burner management system in a stand-alone ControlLogix PLC. The IPP specified that process safety and stability were a premium due to past challenges from the original prototype incinerator. Therefore, process and control engineering design, testing, construction, and startup services were provided for a completely new and upgraded control system. Included in these services was the development and finalization of the functional process organization for H2S abatement.

RESULTS


• For this DCS upgrade, the field device input/output database was developed implemented and completely managed using Microsoft Access.

• Designed an automated lead/lag motor start for a set of three combustion blowers. The logic automatically chose lead/lag/standby based on operator selected parameters.

• Designed a "simple" versus "complex" analog control logic with cross tracking for combustion air flow based on fuel/air ratio, O2 trim, and cross correction with fuel.

• Built operator graphics for the H2S incineration process and control system. These included standard auto/manual control stations and P&ID indication graphics.

• Conducted final construction inspection, all control system loop checks, systems startup testing, and final commissioning to full operating status of this replacement H2S Incinerator.